General
The IQ includes comprehensive diagnostic tools. The IQ display includes four dedicated Icons indicating group Control System, Actuator and Valve alarms. A battery icon also will display a battery low condition. Refer to publication E170E.
IQ Insight Actuator Diagnostics analyses the alarm status of the IQ and reports back both group alarm status and a breakdown of specific alarm conditions.Diagnostics can only be used when connected to an IQ
Back to IndexBegin Diagnostics
Click the Begin Diagnostics control to interrogate the IQ for the current alarm status.
Insight will indicate current alarms by highlighting the applicable group alarm:Control Alarm - remote control system applying an active ESD or interlock signal.
Actuator Alarm - actuator detects an internal fault or power supply problem.
Valve Alarm - valve is jammed or obstructed mid travel causing a torque trip.
Battery Alarm - actuator low battery condition or battery test problem.The specific cause of the alarm(s) will also be highlighted. If there are no alarms, Actuator Diagnostics will show all group alarms off and specific conditions as OK.
The tables below provides an specific alarm condition action/check list:
Control Alarm ConditionAction/Check ESD ActiveIQ performs set ESD action and is inhibited. Check ESD set-up in Configuration and remote ESD signal status. Close/Open Interlock activeClose and/or Open operation inhibited. Check interlock set-up in Configuration and remote interlock signal status.
Actuator Alarm ConditionAction/Check EEPROM Pos. data corruptReset Limits, Power down/up and check for alarm EEPROM Calibration. data corruptContact Rotork EEPROM Configuration customer. data corruptCheck defaults (Configuration) and re send settings back to IQ. Power down/up and check for alarm Local control ErrorCheck local control action Thermostat trippedAllow motor to cool and re-check Phase loss detectedCheck power supply to actuator Position status errorContact Rotork Torque transducer errorContact Rotork Watchdog errorContact Rotork Error in local and remoteCheck local/remote control action Error in local while in remoteCheck local/remote control action
Valve Alarm ConditionAction/Check Valve JammedActuator could not move valve from its open or closed position. Check valve operation using handwheel. Torque trip Open/CloseActuator tripped while closing/opening between set limit positions. Operation in the same direction is inhibited. Check torque switch setting in Configuration. Check valve operation using handwheel.
Battery Alarm ConditionAction/Check Battery low on power upOperation Inhibited - check Power Loss Inhibit setting (Configuration - protection settings). Reset limits. Replace Battery. Reference to E170E must be made before changing the IQ battery. E170E provides information on battery types and replacement. Battery LowReplace battery. Reference to E170E must be made before changing the IQ battery. E170E provides information on battery types and replacement. Utility Commands
Print - Prints alarm status report to the Windows default printer
Copy - Copy status to the clipboard